Presentation: Thames Water: Moving to a Standardized Modular Approach for their Site SCADA Applications with AVEVA System Platform

2024 - AVEVA World - Paris - Infrastructure (Water, Facilities, Transport, Marine, DC)

Thames Water: Moving to a Standardized Modular Approach for their Site SCADA Applications with AVEVA System Platform

A program to replace Thames Water’s various legacy systems was deployed across 50 sites using the AVEVA System Platform product.  It employed a templated / standardized approach and was scaled to fit systems of varying size. In addition, Thames’ internal governing SCADA standards were updated and adopted throughout delivery on the new systems.  This approach aimed at providing consistent database construction and visualization across the estate.


Industry

Water and Wastewater


Company

Thames Water

Speaker

Alex Gray

Dr Alex Gray BEng (Hons) Ph.D. CEng MIET Starting his career as an apprentice electrician, Alex is now a chartered electrical and control systems engineer. He completed his degree in power engineering, which he followed with a Ph.D. at Brunel London. His research used AI-ML techniques to optimise a wastewater catchment with a focus on energy reduction. In recent years, he has led large delivery programmes involving complex multi-disciplinary upgrades within the utility sector. He now works as Head of Operational Technology at Thames Water which sees him leading the team that runs the automation and data layer for the largest UK water and waste company.


Company

Thames Water

Speaker

Stephen Wigley

Stephen is a chartered engineer working at Thames Water, he leads the technical teams within operational technology. He has worked in various roles including architecture and network engineering at Thames Water for over 22 years. He is the technical lead of a range of research and development trials within the business including communication technologies such as NBIoT and IoT protocols such as MQTT. He has a particular technical strength of communication networks and connecting systems together to meet business requirements, whilst also able to bring teams together around a central vision. 


Session Code

AW24-INF-D2-SESS-314

Transcript

Good afternoon, everybody. Let me just make sure I'm familiar with the tech and that I'm not gonna make any silly mistakes.

 

No. It's looking good.

 

Okay. I am gonna start with pointing out potential oversight from the Aviva marketing team looking at the location we're at. Why the hell this wasn't called Aviva La France? I have no idea.

 

But one one to take away when we come back to France next time around, if that's possible. And I do have to give credit to Neil for that one. I didn't think of that. Thank you, Neil.

 

Anyway, I just needed to get that one in there. So who are speaking today? So I'll hand over to Steve first to introduce himself, and then the mic will come back to me.

 

Yeah. I'm Stephen Wigley. I'm the OT technical manager, and good afternoon.

 

And I'm Alex Gray. I'm the head of operational technology at Thames Water.

 

So I'll run you through the agenda quickly. I'm gonna take us through who Thames Water are for those of you who don't know. I'm gonna talk a little bit about our position before we adopted the Aviva system platform product, and And then I'm gonna hand over to Steve who's gonna really take us into the the more technical aspects of how we achieve that through the architecture standardization, etcetera. And then a little bit at the end about what it is we want to achieve going forward, in in in what is hoping to, shape up to be quite a transformational period for Thames Water.

 

So Thames Water is a large water company in the UK. I actually think that, globally, we are in the top three in terms of operational technology, install base, the amount of SCADA systems, data points, etcetera, etcetera. And I will make a a declaration here. That's not because we are good and we have earned the right to that.

 

That's because in nineteen ninety four when Margaret Thatcher decided to privatize the UK water sector, someone in a war room had a Sharpie pen and just drew a big circle on the piece of the map. And that's why we are as big as we are. But notwithstanding, it's massive. Two point six billion liters of water a day, we produce and distribute to our customers.

 

That's the equivalent of a thousand Olympic swimming pools every day. And we treat the waste product of nearly double that at four point seven billion liters a day. So it's huge. We serve ten million water customers.

 

So not as our waste customer are our biggest customer, sixteen million. Ten million of those customers. So it's not twenty six million in total. It's sixteen million customers in total, of which ten million are consumers of water.

 

In terms of operational technology, SCADA systems, we have a a very disparate install base using some well, we did have a very disparate SCADA install base using some very legacy technology out in the field as as the the little emoji with the eyes will point out. We had some very old Windows two thousand. I actually think some of our original starters were running on Windows NT. They were very isolated.

 

So the SCADA systems, they just it was on the site, and it gave whoever the op the the ability to operate the pumps, trend pens, whatever. But there was no sort of centralized connectivity for one, you know, for us to take a more holistic look over our state. So, pressing on into just how desperate that was, and apologies that the the text has shifted on the slides. But, I I know I'm not allowed to stand over this line, but what I wanna point out is this is how desperate it was.

 

These are all individual, discarded databases that we see dotted around, the the the catchment helping us to serve sixteen million customers. And I wanna point out a special one here, this Intellution. This was an Intellution fixed SCADA system, whereby there was an operator on that site. His name is Keith.

 

And Keith would use SCADA once a day. He would walk in.

 

He would flick the mouse.

 

That would wake up the screensaver. It would go straight onto the page he wanted. He would he would take down the SAS reading, so surplus activated sludge. He would get that reading.

 

He would write in a book. That's him. He's done. Scarder done, and he's off, and he's doing the rest of his stuff for the rest of the day.

 

Brilliant.

 

We will come back to Keith a little bit later.

 

I wanna point out, however, though, Frank and Sally in the control room here, they're using a different product. It's an industrial defender product, something we called RTAP. Now that's where Frank and Sally would sit for twenty four hours a day operating Ashford or Kempton. Now these are sites that are chucking out about five hundred to eight hundred megaliters per day. It's a huge amount of water that we're putting into the capital of the UK, and Frank and Sally use it twenty four by seven. So we've got a huge spectrum of different SCADA users in our patch, which was which which did lead to making it quite difficult when it came to trying to enact that change and and and get ourselves away from what is a very disparate system.

 

There we go. No system the same. So this is, like I said, they're all very different.

 

The technology why were they different? So the technology at the time would sometimes be flavor of the month. Okay? So we didn't have a SCADA program that was like, right.

 

Let's go out and put SCADA into this site. What would happen is we're gonna install a digester plant or we're gonna install a GAC plant, or we're gonna install this plant. And as part of that growth scheme, there was a need for SCADA. And so the capital delivery partner would say, right.

 

Well, we're chucking you know, we're spending, I don't know, ten million on on the plant, and half a million would be for some OT, PLCs, and whatever. And the capital delivery guys and girls would just go, what's the cheapest? And that's what's led to us getting Intellution or or RS View or Iconix. And it it's been a very organic growth.

 

And also, it'll be different system integrators doing the delivery. And one person's, you know, opinion on what a pump looks like might be different to what another person's opinion on what a pump looks like. And what that led to was some I'm going backwards and not forwards. So here's the example of how different some of the pumps were.

 

So we look at the top two here. That's a pump, but someone might think that's a fan or a blower.

 

And so the fact that we could go around our entire estate with different graphics, but they all represent a pump, was becoming an issue. And and the more the more we become automated, the more our operators traverse across different sites. So perhaps back in the day, an operator would be you're assigned to that site. But actually, automation means that we are able to use our resource more efficiently.

 

So now not not so much Keith, but if I think of, like, Bob, Bob might be now going across different sites. And so when Bob goes to site a and he sees this, and he's used to this being a pump, and then he goes to another site and he sees this, he doesn't doesn't know what it is. Or at least he needs to ask someone. He's very inefficient.

 

So we had some issues with that as well. And I think I got one more example of a really, really different one. So that's a sludge screen, apparently. Looks like a circle.

 

And then that's another sludge screen. Looks like a motor. Similar issues. So this was really, really beginning to build and be compounded into providing issues in the sense that we did not have a standardized approach within our our Skarder estate.

 

So enough was enough.

 

We made a decision. Our asset, let me try and give you a bit on the asset management plan. Within the UK, we do five yearly investment periods. So every five year, we tell our regulator, we need to spend this much to do this for our customers to reduce leakage, to reduce pollutions, and to keep our assets operational.

 

In the p r o nine plan, we put in a significant sum of money so that we could do what is called the AMP five SCADA program. And that's where we began to go and replace those SCADA systems into a standardized modular approach.

 

And so by twenty fifteen, we were very we were successful. We had pretty much upgraded most of our site SCADAs. Then we went into round two of upgrades into twenty fourteen r two. And here we are today in twenty twenty two at Aviva World, starting to patch to twenty twenty two.

 

And also there's some other stuff with pie and I mean, the the previous presenter was talking about, you know, being able to tweak slides since walking the shop floor and seeing all the incredible technology, I would have probably liked that as well because there's some stuff with Connect and Process View. And there's a lot of stuff that we can do once we get get these up upgrades done. And perhaps when we come back, we can show you all the stuff that we've done in this next transformational period. But before I go into that too much, I am gonna now pass over to Steve who's gonna go into the technical aspects of what we did.

 

Steve.

 

Thanks, Alex. So so Alex has, gone through the the what and the why. Hopefully, I'm gonna give a bit of an explanation on the how. So back in two thousand and eight, a few of these standards went out there. So we looked at what we had in place. We've got, three things I've I've put up there. So we have the the OT technology strategy.

 

We had the regulatory standards, which we were guided by. And back in two thousand and eight, there wasn't the NIS, wasn't out. A lot of the cyber maturity wasn't yet established, but there was guidance out there. We used we used those materials, and we also looked at the in flight programs. Now we understood that network segmentation, boundary controls, security controls were important for a scheme like this, and also remote access to our assets was fundamental.

 

We also understood that alarm reduction was needed, that alarms were out of hand. They weren't standardized.

 

The SCADA signal integrity wasn't necessarily all there, and it was different standards across the board for each of those different four different systems.

 

So what we did is we collected all of that data, and there was a little bit of data, but it was of varying qualities of those four systems, and started consolidated that down. And there you see a few of our standards that we started to develop.

 

And we there's kind of two themes that we looked at, that I wanted to sort of draw your attention to. One is standardization and one is templates.

 

These are the two themes that we we built on to build out our system platform.

 

So we had our site starter kit. This tells us how we build a system, and it's always the same, always the same templates. We have an OTL, what we call internally as an OTL, an object template library. Again, that standard for every site. We have fifty two sites today, and they all use this OTL, all templated, all there to be used for the site specific details.

 

And we do have, an object library and a tagging standard too.

 

So just to go diving in a bit of detail, I'll go through our architecture, and this is a mix of twenty fourteen and twenty twenty three, just to give you a bit of a flavor. But we use the Purdue stack to try and represent data flows. Yes. IoT has kind of messed about with that a little bit, but it's good for understanding relationships and data flows. So down the bottom, we've got shown there is a chlorine analyzer, and that goes into a PLC or remote IO and up into a PLC. We use Rockwell in TEMS, and that goes into our application server.

 

And within that application server, we run Kepware and system platform.

 

I'll come on to Kepware in a bit more detail in a minute.

 

But within that, we have, that within that system platform, we have two other virtual machines, a historian and a terminal server, and then we have our thin clients. Thin clients are just really a window into the terminal server for the local site controller.

 

We then have a read only domain controller. This means our site can use role based access controls even when there's no WAN connection.

 

We also use, SRA. We use Clarity secure access to be able to remote into those terminal servers. And today, we have a a a new cluster, which is our read only terminal servers, which allows for remote access to give read only, throughout the design and architecture.

 

From our historian, we also feed that data into Aviva tier two historian. So all of our sites collectively feed into that, for both time series and alarming events. And we use Aviva reporting.

 

We also link our read only domain controller interactive directory, so we've got global administration of all of the users.

 

We have around seven hundred users, within this, and they're all managed centrally, through this platform.

 

And I mentioned Kepware, and I'll come back onto that.

 

Where we don't want signals necessarily in SCADA right now, we may want that data to be fed into an insight layer into our, into our corporate environment. Things like power monitoring, vibration detection, not necessarily used for the here and now for for the control room, but still very much needed by the business. We can bring that data through Kepware and MQTT protocols straight into our data streaming server and into the IT enterprise, without cluttering up the SCADA application.

 

So that just goes through every site is the same. Those fifty two sites, they're all the same, same architecture.

 

But, I'll just go on to what we would do for a large site SCADA. So, we have two templates, a small and a large. So, a large looks like this, has multiples. So, what we have is, we have a distributed system, two hypervisors with the VMs all supported. We then have all of those linked together, and then thin clients in the control room, with the window into the terminal server. Now, we currently have our Aviva Pi in the IT enterprise layer, along with our email server and corporate landing server. We're working, and and I'll come on to the vision and a bit of what we're doing with those.

 

Now, a lot of this, architecture is around high availability, and we need to be always on. We cannot our control room complain if our failover isn't within ten seconds that we we don't that they don't like it. And within if it's greater than a minute, then we don't meet our regulatory obligation.

 

So what we do is, we create high availability throughout, and that allows us to patch and manage these assets that these are running on without having downtime on the site.

 

So things we looked at to take forward.

 

So we've, we use virtualization.

 

We want to take more of that, onboard. That's helped us be able to upgrade our system. So we've gone twenty twelve, twenty fourteen, twenty twenty three. That virtualization allows us to dual run, create the twenty twenty three VMs, build, test, deploy, hand over to control room, they can dual run. One o'clock at the in the morning, something goes wrong with the new system, they can fail back to the new the old.

 

Any issues, they can swap and change. After thirty day run period, we can then delete.

 

We also used Microsoft SCCM extensively, so we don't just build a new VM from scratch anymore. We just hit task sequences and go deploy. This is a terminal server. Deploy. This is a historian server. This is its name. Build.

 

And that means that every site, every VM is exactly the same.

 

It just has the site specific code deployed on it for that Pacific Galaxy.

 

We also have UPS autonomy, which we link into to globally shut down the VMs. And also, we have the two architectures which I was talking about, the small and the large.

 

Also, the RBAC controls and the network design.

 

Again, segmented and to try and create segments of cybersecurity, with edge controls.

 

And, yeah, that's quite a lot of what we, learned about, and, I'll pass over to Alex.

 

Thank you, Steve. So, yeah, very technical. Lots of lessons that we took away from a technical perspective. But lots lots of also sort of cultural lessons that we took away in in developing that. And I I'm gonna bring you back to Keith. So Keith moved the mouse, got his reading.

 

Now we've deployed a client on the site that you have to log into through AD credentials.

 

You then have to spin up a an RDP session, and you have to then log into the application. So Keith has gone overnight from having to flick his mouse to get his SaaS reading to having to remember a password, which is frustrating for some.

 

Do that two times, then log in to an application.

 

And so this was I was actually on the delivery teams before I worked for Thames. I I was part of the, the program team that were delivering this. And and a fundamental lesson that we learned was delivering it to them is wrong. We have got to engage our clients way, way earlier on. Because, look, I I'll be honest. Keith is always gonna be upset with me for making him log into a client RDP application when all he has to do is flick the mouse.

 

But if I talk to him and I understand that he has his own limitations with computer literacy, and we can arrange training and bring him you know, work with him to say, look. Yeah. Explain to him why we're doing it. Security. Explain to Keith that, actually, Keith, when you're on holiday and Frank turns up and knocks the mouse and looks at the SAS reading, Great. But what happens if Frank then goes on to the digester page and runs a pump against the closed valve?

 

You're logged in. It's your cash credentials.

 

You're accountable.

 

So explaining things like that, taking our customer on the journey early doors, helping with any training rather than just rocking up on-site with a new shiny box, putting it on the site and saying, there you go, Keith. Log into that and let's now you go. It failed. It did fail. And and that's just one example.

 

I'm sure I could give you a few examples, but, conscious of time, one one other example was a really interesting one, and it was actually on our big water production plant Hampton. I got door stopped by one of the operators, on my way to do some commissioning on on one of the Skarders. And I just happened to say, how is it? How's the scarder going?

 

And he just said, shit, mate. Like, okay. It was it was okay. So it was an immediate sort of bit of aggression.

 

And I I just took it upon myself to say, why? Like, what is so bad about it? Well, this and that.

 

And, I said, alright. Let's let's go sit down. Sit down. So some colors of a trend pen were wrong.

 

Change colors of a trend pen. This mimics wrong. Well, what's wrong with it? Well, I don't like that.

 

Okay. Change it. We can do these things. And so that's not a slight on him.

 

He he was upset because we'd given him a new thing and hadn't talked to him early doors. If we had spoken to Bob and said, we're doing this. What is it you want? And he said, well, I like that color, and I don't want that color.

 

It would have been a much easier pass at getting it over the line, in in the early days. And we did this on fifty two sites, and we pretty much I think out of the fifty two sites, we only got one or two signed off on on takeover certificate at at stage one. The rest of them, comments, comments, comments, action. And actually, the big sites were, I think, a year in going back and forth between us and the end user to get ourselves to a, to a point in time where we, could sign off and and hand the system over. So take the customer on the journey from day one. Don't don't deliver it to them at the end was my number one learning on that program. So I think I'm gonna quickly pass back to Steve who's gonna talk about some of the deficiencies technically.

 

So, yeah, just to, run through three of the issues we had, especially going from twenty fourteen to twenty twenty three.

 

One was remote access. A lot of that is cybersecurity.

 

How does that get delivered? Twenty two thousand and eight to twenty twenty three? Very different. And that was a particular challenge because because of the way we had architected it.

 

Also, data integration. We'd used OPC HDA, and we wanted to move to UA.

 

And also some of our reporting, was was no longer supported, so we were looking at alternative methods for that. So we've taken these on board to go, well, okay. If we had had it again, how would we re architect it? And also using that feedback into our decisions moving forward.

 

So what's our vision for two thousand and thirty? So you've seen our architecture as it is now. What are we looking at? So we understand that there's two data streams, really. We've got time series data, and we've got alarm and events. And the way you handle and manage those are very different.

 

And so you can recognize the the level three. That remains unchanged.

 

But what we're looking to do is, move that Aviva Pi solution from IT and move it into OT.

 

What that means is we can remove the time series data out of our Aviva tier two historian and move it into Aviva Pi. That allows us to master our device or asset framework in system platform twenty three, which will allow us to add tags in system platform, and that will automatically be in Aviva Pi in the same structure, in the same way that it is in SCADA, in that same object orientated methodology. That allows the users of SCADA to be able to interchange between products, but still be used to the same tagging standard and the same structure.

 

Also, we're looking at alarm and event management and how we can get those that data still using the tier two historian, Aviva tier two historian, to manage our alarming events and be able to feed off of that data into applications above that will allow us to manage and maintain those.

 

I've spoken a lot about system platform. System platform is across fifty two of our sites, manages one point one million tags.

 

We also have a thing what we call regional SCADA.

 

It's currently Schneider Electric. Clear SCADA handles roughly about one point one million tags as well, so about fifty fifty split.

 

And the difference between this is that system platform only has process values coming to it. Once it receives a process value, it tags it it with a time stamp.

 

With our Schneider Electric ClearSCADA platform, that's time stamped way back at site. And when it communicates to ClearSCADA, it transmits both process value and the time stamp that that process value was taken and backfills that in history.

 

So we've got these two point two million data points from our regional and our site systems, and we're looking to amalgamate them both into the Aviva PI platform and the tier two historian for alarm and events. That allows us to have the same view across both our systems.

 

A big part of that, though, is to get that tagging right. So within our system platform, a lot about that was tagging standards. Within our regional system, it's quite a mess. And so we're gonna have to retag pretty much our entire asset base in that one point one million tag base, and then get it in getting it in the same name space as our system platform. That allow us to mix and match both systems and be universal and almost be system agnostic over which ones we're gonna be looking at.

 

So that's really the architecture.

 

All of this couldn't be done without the OT team at Thames. Infrastructure team, network teams, compute teams, application data teams all had to be built around this to get this to where it is. It hasn't been just technology. A lot of it hangs, or all of it, hangs on the people we have. So from that, I'll hand over to Alex to finish off.

 

Thank you, Steve. So I'm conscious that we have actually hit time. This is the summary slide. So the challenge I've talked about, we had disparate scarders all over the place. We needed to we needed to upgrade them. We needed a central, standardized, modular SCADA application, which we deployed through system platform, and it's been very, very successful.

 

Probably the one of the most successful parts of doing it was the fact that we've now got asset hierarchy. So the data is context rich. It goes from site to process area, to asset, to number, to attribute, all within a common framework that we've deployed. We're using that framework to go forward into rebuilding our three GeoSCADA products, NexStamp, as well as doing things about putting pie in on the on our side of the DMZ.

 

It's it's exciting. It's scary as the head of OT and understanding what we're gonna be doing to some of our customers and and all the stuff that goes with huge transformational programs. But by the end of it and having a unified a unified name space is gonna absolutely put terms ahead of the curve, unable to do AI, unable to do this. Because I'll I'll pay it very, very quick acknowledgment to AI.

 

Currently, we're sending data from our systems into the cloud, which you would create data products over. But those data products are auxiliary to our SCADA. They don't integrate into the UAC.

 

We need to be the masters of the data management. Our side of the fence, allow wonderful products like Connect to drive the analytical dashboards that then our corporate users can do rather than just data product, data product, data product. And I wish I put a photo in because I've got a fantastic photo of an operator at one of our sites.

 

He's looking at his SCADA screen. He's got six screens in front of him, and that's his SCADA well. That's his, you know, that's that sort of stuff there. But all of a sudden, appeared to the right is this data product that tells him some pump efficiencies.

 

And great. It's good intelligence, and we need that intelligence. But you're asking the guy to look over here for five minutes to look at some intelligence. All the while, he's not looking at his world of influence, alarms, control, you know, where stuff goes wrong when he has to react.

 

So UOC is a big thing that we want to adopt, and I think by doing our GeoSguider upgrade in line with the way we've done our Wonderware, sorry, system platform upgrade, we are gonna be able to achieve that.